How Often Does a Restaurant Hood Need Cleaning? The NFPA 96 Schedule

Ask ten restaurant owners how often their exhaust hood has to be cleaned and you will get ten answers, most of them “whenever the guy calls.” NFPA 96 has an actual schedule, it depends on what you cook and how long you cook it, and the fire marshal knows it by heart. Here is the schedule, what a real cleaning involves, and why the fan on the roof matters as much as the hood over the line.

Why the Hood Is the Fire Problem

Cooking equipment is the leading cause of restaurant fires by a wide margin — U.S. Fire Administration data puts cooking at roughly two-thirds of restaurant fires, and NFPA’s figures for eating and drinking establishments have cooking equipment behind more than 60 percent of them, with property losses running well over $100 million a year nationally. Most of those fires start on the cooking line. The dangerous ones climb into the hood.

Grease vapor leaves the fryer and the flat-top as an aerosol. It condenses on the filters, the plenum behind them, the duct, and the fan. Over weeks it builds into a layer that is essentially solid fuel lining a chimney. A flare-up that reaches the filters ignites that layer, and now the fire is moving through the duct toward the roof, out of reach of the suppression nozzles and out of sight of everyone in the kitchen. That is the fire that closes restaurants for good. Hood cleaning exists to take the fuel out of the chimney.

The NFPA 96 Schedule

NFPA 96, Standard for Ventilation Control and Fire Protection of Commercial Cooking Operations, requires the entire exhaust system to be inspected for grease buildup on a schedule tied to the type and volume of cooking:

Type of cooking operationInspection frequency
Solid fuel cooking — wood-fired ovens, charbroilers burning wood or charcoalMonthly
High-volume cooking — 24-hour operations, charbroiling, wok cookingQuarterly
Moderate-volume cooking — the typical full-service restaurantSemiannually
Low-volume cooking — churches, day camps, seasonal businesses, senior centersAnnually

Two things about that table. First, it is an inspection frequency, and the inspection has to be done by properly trained, qualified and certified people acceptable to the authority having jurisdiction — not the dishwasher with a flashlight. Second, if the inspection finds grease deposits, the system gets cleaned. In practice, for a working restaurant, the inspection and the cleaning are the same visit. A moderate-volume kitchen that runs a fryer and a flat-top through lunch and dinner is on a six-month cycle, and a busy one is on three.

The standard also gives a number for what “dirty” means: measurable grease of 2,000 microns — about 0.078 inch — anywhere in the system triggers a cleaning. Inspectors carry a depth gauge. So do we.

What a Real Cleaning Involves

A hood cleaning is not wiping the stainless and swapping the filters. NFPA 96 requires the system to be cleaned to bare metal — hood, plenum, duct and fan — and the work runs top to bottom.

The crew tarps the line and the floor, pulls the filters, and opens the access panels along the duct. Degreaser goes on and gets time to work. The hood interior and plenum are scraped and pressure-washed, the duct is washed through the access panels from the hood up to the roof, and the fan is opened and cleaned inside the housing and on the blades. On the roof, the grease that has been dripping out of the fan gets dealt with, because a grease-soaked roof around the fan is its own fire and its own leak. The system is rinsed, the polish goes on the stainless, the filters go back, and the crew leaves a dated sticker on the hood with the company name and a note of anything that could not be reached.

That sticker is not decoration. NFPA 96 requires a record of the inspection and cleaning to be kept on the premises, and the fire marshal will ask for it. Ours goes on the hood, and a written report goes to you. The full process is on our commercial hood cleaning page.

The Fan, the Hinge Kit, and the Roof

The single most common thing we find on a first visit to a new customer is a fan that has never been cleaned. Hoods get wiped because they are visible. Fans sit on the roof, out of sight, accumulating grease in the housing and on the blades until they are out of balance and dripping onto the roofing.

NFPA 96 requires rooftop exhaust fans to be hinged so they can be tipped back for cleaning without disconnecting the ductwork or the wiring. A lot of older fans in this part of the country are simply bolted down. We install hinge kits as part of the job, and after that the fan gets cleaned every visit instead of never. If your fan is not hinged, ask whoever cleaned your hood last time how they cleaned the fan. The honest answer is usually that they did not.

Filters Between Visits

Between professional cleanings, the baffle filters are your job. They are the first thing grease hits, and they need to come out and go through the dish machine or a soak tank regularly — weekly in most kitchens, more often on a charbroiler. Filters that are packed with grease do two things: they stop capturing it, so more goes up the duct, and they become fuel sitting directly over the flames. Mesh filters are not permitted under NFPA 96 in grease applications; if yours are mesh, replace them with baffles.

The Hood and the Suppression System Are One Job

Above the cooking line, two systems share the same space: the exhaust hood that removes the grease, and the fire suppression system whose nozzles are aimed at the appliances and up into the plenum and duct. They are inspected on the same six-month cycle — NFPA 17A for the suppression system, NFPA 96 for the hood — and they fail each other. A grease-loaded duct is more than the suppression system was designed to protect. A nozzle caked in grease does not discharge properly. A fusible link buried in buildup will not melt when it should.

That is why we do both on the same visit: the kitchen fire suppression inspection and the hood cleaning, one company, one invoice, one set of paperwork for the marshal. Kitchen work happens before service or after close, so the line is never down while you are trying to feed people.

What Happens When It Goes Wrong

If the system discharges — because a fire reached the fusible links, or because someone hit the pull station — call the fire department first, even if the fire is out. Leave the gas and electric off. Do not scrape or rinse the agent off the appliances, and do not fire the line back up. The system has to be recharged, the links replaced, the detection retested and the residue cleaned off the appliances before the kitchen can legally cook. Discharge calls go to the front of our queue, because until that is done you are closed.

Getting on a Schedule

Figure out where your kitchen falls in the NFPA 96 table, check the date on the sticker in your hood, and if there is no sticker, assume you are overdue. We clean hoods, ducts and fans across Wisconsin, Iowa and Illinois — the restaurant rows of Madison and Milwaukee, the riverfront kitchens in Dubuque and La Crosse, the college towns of Iowa City and Cedar Rapids — on a route we have run since 1975. Tell us what you cook and how many hours a day, and we will tell you which line of the table you are on.

Questions We Get Asked

How often does my restaurant hood need to be cleaned?

Under NFPA 96 it depends on what you cook and for how long: monthly for solid fuel, quarterly for high-volume operations like 24-hour kitchens, charbroilers and woks, every six months for a typical full-service restaurant, and annually for low-volume kitchens such as churches and seasonal businesses. If an inspection finds grease deposits, the system gets cleaned regardless of the calendar.

Is hood cleaning required by law?

NFPA 96 is adopted by the fire codes in Wisconsin, Iowa and Illinois, so the inspection schedule and the bare-metal cleaning requirement carry the force of the local fire code. The fire marshal will ask for the dated sticker on the hood and the written record, and most insurance policies on restaurants require proof of cleaning as well.

What does “cleaned to bare metal” mean?

It means every grease-contact surface in the system — hood interior, plenum, duct and fan — is scraped and washed until the metal is exposed, not wiped down or spot-cleaned. A wiped hood over an untouched duct is the most common shortcut in this trade and the most dangerous one, because the duct is where the fire travels.

Can I clean the hood myself?

You can and should keep up with the baffle filters between visits. The inspection and cleaning of the system as a whole has to be done by trained, qualified and certified people acceptable to the fire marshal, with access to the duct and the fan. Most owners who try it end up with a clean hood, a dirty duct and no paperwork.

Why does the fan on the roof matter?

Because it is the last stop for every bit of grease that left the cooking line, and it is out of sight. An uncleaned fan runs out of balance, drips grease onto the roof, and is the part of the system most likely to be burning when the fire department arrives. NFPA 96 requires it to be hinged so it can be cleaned properly; we install hinge kits where they are missing.